Component Testing
All of the components in an electro-mechanical system are switches. They are either on or off. How they are controlled and what turns them on or off varies between designs and manufacturers.
The following are simple overviews of the most common components.
Never test components with power applied to the hot tub. Be aware your system may vary.
Thermostat
A thermostat is a simple switch. It is either on or off. Unlike a light switch you turn on by hand, the thermostat has a sensing bulb attached to a capillary tube which is attached to the thermostat switch. The sensing bulb and capillary tube are gas filled. As the gas warms, it expands and activates the switch. The knob on the switch, tells the switch at what level the gas temperature should activate the switch.
Testing: Turn spa power off and remove wires from thermostat. Turn Thermostat up as far as it goes. test for continuity across the two terminals using a voltmeter (multimeter). If continuity is present, and spa water is below 104 degrees, Thermostat is working at that temperature. If no continuity is present, the thermostat has lost calibration and should be replaced.
If Spa water is 104 degrees or above and there is no continuity across thermostat, the thermostat is going to allow the water to continue to heat. Watch carefully, if the water temperature increases above 104 plus or minus a degree or two, replace the thermostat. Hot Tubs and Spas should never be used at temperatures above 104 degrees.
Note: Thermostats may test properly at some temperatures but not at other temperatures. They can lose upper or lower end calibration. If you find a thermostat not working properly or working erratically , no matter what the temperature is, you should replace it.
High - Limit Switch
A high limit switch is exactly that. A switch. It is either on or off. High limit switches are safety switches that will turn power off to the spa heater in the event the water temperature exceeds 118 degrees. Now, you need to be aware that by the time a high limit switch trips ( or opens ) to shut power off to the spa heater, the water temperature is high enough to burn your body severely. Always use a working thermometer in your spa and always check the temperature prior to entering the water.
Testing: Turn power off to the hot tub. Remove wires from the high limit switch.
If water is below 104 degrees, There should be continuity through the switch. Test using a multimeter and touching one lead to one terminal of the switch and the other lead of the meter to the other terminal of the switch. Continuity means that the switch is closed and will allow power to flow through it.
If there is no continuity, check the red button and see if it has popped out ( tripped to shut power off ).
If the red button is out, the high limit has tripped. This can be caused by several things, but basically the water is too hot. The high limit sensing bulb does not test the actual spa water temperature but instead tests the water temperature in the heater vessel. A plugged filter not allowing water to move fast enough through the heater vessel can cause a high limit switch to trip.
If the red button has not popped out, and there is no continuity between the high limit terminals. The high limit is bad and should be replaced.
Pressure Switch
A pressure switch is another switch used to control the heater of the spa. It tells the system that it is either ok for the heater to come on or that it is not safe for the heater to come on.
Testing: Power must be on and spa running to test a pressure switch. There are two terminals on the pressure switch. Turn power off to spa, remove wires from the pressure switch, tape the ends of the wires to avoid shorting when power is turned on. Turn power on to spa, test for continuity between the two terminals of the pressure switch. Using a multimeter, place one lead on one of the terminals and the other lead on the other terminal.
If you have continuity, the pressure switch is activated, telling the system it is ok for the heater to come on.
If there is no continuity and the pump is running, and you have adequate water flow, the pressure switch is not activating and should be replaced.
Turn power off to the hot tub. Retest pressure switch. When testing for continuity with the spa off (no pump running) you should not have continuity across the switch. If continuity is present, replace the switch. it is stuck in the closed position
Contactor
A contactor is a switch controlled by a coil. When there is voltage across the coil it will cause the contactor contacts to pull in allowing power to flow from one side to the other completing a connection.
There are usually 4 large connections on the top of the contactor. These are the contact connections. two are input and two are output. When voltage is applied to the input contacts and the coil is energized the contactor will close a bridge between the input and output contacts completing the connections and allowing power to flow through it.
Each contactor has a coil that controls it's operation. One side of the coil will connect to the common or neutral wiring. the other side will connect through switches like the thermostat, high-limit and pressure switch. If all switches are closed, the coil will energized and close the bridge on the contactor.
Testing: You must have power on to test a contactor operation. Extreme caution should be taken.
Test for voltage at the input terminals. Using a multimeter place one lead on one of the input terminals and the other lead to common or neutral on the source incoming power bar.
If voltage is present, check for coil voltage. Coil voltage could be any of the following:
120 volts AC
240 volts AC
120 volts DC (rarely but some manufacturers use it)
Once you know the coil voltage (should be stamped on side of contactor) you can test the coil by placing one lead from the multimeter to one side of the coil and the other lead from the multimeter to the other side of the coil. Coil connections on the contactor usually look like spade connectors and are on the side of the contactor.
If you have proper voltage, test for voltage on theinput and output contacts of the contactor. You should have the same voltage on both sides of the contactor when the coil is energized. If voltage is different or no voltage is present on the outputs when voltage is present on the inputs the contactor is bad. Replace it.
If you do not have proper voltage on the coil connections, you can not test contactor operation. Follow control circuit for coil connections.
Air Switch
Air Switches are another type switch found in electro-mechanical control systems. They are activated by air pressure from an air button usually located at the top of the spa for easy access to the user. Air switches remove the need for electrical buttons at water level for safety reasons.
Air buttons usually have 2 or 3 connections. We will look at a 3 connection button for a two speed pump.
Connection one is "Common" ( comm ) power into switch.
Connection two is "normally open" (NO) High speed pump.
Connection three is "normally closed" (NC) Low speed pump.
Testing: If power is available at terminal 1 on the air switch, power should be available at terminal 3 of the air switch. Pressing the air button should activate the air switch and move the power from terminal 3 to terminal 2.
Using a multimeter place one lead on the common of the source power bar of system and one lead on the "comm" terminal. If voltage is present, place the lead from terminal 1 "comm" on terminal 3 "NC".
If voltage is present, press air button and check switch operation. Voltage should disappear from terminal 3 and appear at terminal 2 "NO".
Malfunction identification: Faulty switch, won't switch when button is pressed or damaged air tube, air leaks out instead of activating air switch.
Go to top